Examine the Online Catalog of Industrial Supplies for Cabur
INPUT TECHNICAL DATA | |
---|---|
Input rated voltage | 1-2-3x 230-400-500 Vac |
Input voltage AC | 185…550 Vac |
Input voltage DC | 270…770 Vdc |
Frequency | 47…63 Hz |
Current consumption | 2 A (230 Vac) / 1 A (400 Vac) |
Inrush peak current | 20 A |
Power factor | > 0.65 |
External protection on AC line | MT: C-6 A / Fuse: T-6.3 A |
OUTPUT TECHNICAL DATA | |
Output voltage range | 24 Vdc ±1% |
Output adjustable range | 24…27.5 Vdc |
Continuous current | 10 A at 50°C |
Overload limiting | 15 A for >6 s |
Short circuit peak current | 38 A for 0.5 s |
Ripple @ nominal ratings | 100 mVpp |
Hold up time | 15 ms (230 Vac) / 100 ms (400 Vac) |
Status indication | LED "DC OK" / LED "Alarm" |
Alarm contact | dry contact, max. 1A |
Parallel connection | possible |
Redundant parallel connection | possible with external ORing diode |
GENERAL TECHNICAL DATA | |
Efficiency | 91% (230 Vac) / 92% (400 Vac) |
Dissipated power | 24 W (230 Vac) / 21 W (400 Vac) |
Operating temperature range | –20…+60°C (derating -3 W >50°C) |
Input / output isolation | 3 KVac / 60 s (SELV output) |
Input / ground isolation | 2 kVac / 60 s |
Output / ground isolation | 0.5 kVac / 60 s |
Standard / approvals | EN 60950-1 |
EMC Standard | EN 61000-6-1, EN 61000-6-2, EN 61000-6-3, EN 61000-6-4 |
Overvoltage category / pollution degree | II / 2 |
Protection degree | IP 20 |
Connection terminal | 2.5 mm² / 2.5 mm² |
Housing material | aluminium |
Mounting information | vertical on a rail, 10 mm from adjacent components |
The product is a versatile 1-2-3 phase power supply designed for industrial automation and process control applications. It accepts input voltages of 1-2-3x 230-400-500 Vac and provides a stable output of 24 Vdc at 10 A. This power supply features input circuit technology that enhances its immunity to overvoltage conditions, ensuring reliable operation even in the presence of faults in three-phase networks.
It includes multiple protection mechanisms such as short circuit, overload, input and output overvoltage, and over temperature protection, contributing to a high level of reliability. A smart alarm contact signals when the output voltage drops more than 10%, ensuring prompt response to potential issues.
Constructed for DIN-rail mounting, it is suitable for environments that demand robust performance. Its ability to operate within a wide input voltage range of 185 to 550 Vac makes it adaptable to both single-phase and three-phase systems.
- Delivery of spare parts and industrial equipment throughout the USA by Fedex transport company.
- Flexible payment system accepting bank transfers, MasterCard, VISA, PayPall, App Pay, Google Pay.
- Directly from stock and on order.