Voltage relay
SP Set Point of the OVER/UNDER
VOLTAGE control, from 2% to
20% of VN (VN = mains phasephase rated voltage) adjustable
by screwdriver.
If in one phase V<0,6VN, there is
the triggering for phase failure.
ASYM Set Point of the ASYMMETRY
control VM-Vm from 5% to 20%
of VN, adjustable by screwdriver.
VN Choice of the value of VN (mains
rated voltage) among the values
380V, 400V, 415V (for the
MODEL A), adjustment by
screwdriver (the indicator must
be placed in the center of each
of the 3 sectors).
T Timer 0,2÷30 sec. adjustable by
screwdriver, it is activated by the
overcoming of SP or of ASYM
and it delays the triggering of
relay.
During T the leds SP and ASYM
flash.
VISUALIZATIONS
ON GREEN LED: supply on.
SP RED LED: in case of
OVERVOLTAGE it flashes,
in case of UNDERVOLTAGE
it is steady lighted.
ASYM RED LED: in case of set
point overcoming, it is steady
lighted.
L123 YELLOW LED: it is lighted if
the phase sequence is
L1, L2, L3 at pins 5, 3, 1,
it flashes if the phase
sequence is different.
RESET: it is automatic when the
triggering value decreases by 12,5%
for SP or when the ASYMMETRY
decreases by 12,5%.
MODE OF OPERATION
With the regulations on the front it is
possible to fix the value of VN, mains
rated voltage, and it is possible to fix
the triggering values for OVER/UNDER
VOLTAGE and for ASYMMETRY. The
Tab. A shows the SET POINTS and
the matched leds.
REMARK: if the phase sequence is not
L1, L2, L3, the relay is immediately in
alarm.
POSITIVE SAFETY
The relay is normally ON and it goes
OFF when it is in alarm.
INSTALLATION
See the fig. 2.
(Wiring to an electrical board with a
differential relay and a sectionalizing
switch).
The length of every wiring must be less
than 30m.
INPUT: 5-3-1
100Vac or 380Vac/415Vac.
It is requested that the pins 5-3-1
correspond to the phases L1, L2, L3 to
ensure that the relay is not already in
alarm once turned on.
The YELLOW LED L123 must be ON.
OUTPUT: : 1 output relay with two
changeover contacts (5A-230Vac)
resistive load.
- I=3A,V=250VAC,cosϕ=0,7 : 100.000 operations
- I=0,6A,V=250VAC,cosϕ=1 : 1.000.000 operations
- I=0A : 20.000.000 operations (Mechanical Life)
11-10 / 14-15 NC Device not supplied
11-12 / 14-13 NO or in alarm
Insulation between input and contact:
VDE 0110 - IGR C/660
Insulation of the contact:
VDE 0110 - IGR C/250
SUPPLY (pin 3-5)
2VA - 50÷60 Hz. Self-supplied by the
voltage to be monitored.
RANGES
100 Vac, 380 / 400 / 415 Vac.
CASE
• Self-extinguishing ABS.
DIMENSIONS:
45x70x110 mm for DIN rail.
Accessories available on request:
E 405B transparent protection fitted for
tight closure.
WORKING TEMPERATURE: 0÷70°C
WEIGHT: 0,300 kg COLOUR: grey
FUNCTION
The V3-20 must be programmed so
that the VN voltage (phase-phase
voltage of the mains to be protected) is
selected on its front among the values
380V, 400V, 415V.
There are 2 programmable controls:
- The OVER/UNDER VOLTAGE
control.
- The ASYMMETRY control.
With the OVER/UNDER VOLTAGE
control it is checked if at least one
phase-phase voltage deviates from the
value of VN more than what is set with
the SP SET POINT (from ±0% to ±20%
of VN).
Example: with VN=400V (3%→12V,
10%→40V, 20%→80V),
If SP=10%→400V+40V=440V
and 400V-40V=360V are set.
If at least one phase-phase voltage
overcomes 440V, the triggering for
OVERVOLTAGE is obtained. If at least
one phase-phase voltage goes under
360V, the triggering for UNDERVOLTAGE is obtained.
The reset is obtained for values where
∆V=40V is reduced by 12% that is
∆V!35V, thus 435V and 365V.
In the ASYMMETRY control the
ASYM set point goes from 5% VN to
20% VN. 3 phase-phase voltages are
measured, the greatest (VM) and the
lowest (Vm) are chosen, furthermore it
is checked if VM-Vm is greater than the
value set with the indicator.
Example: with VN=400V (5%→20V,
10%→40V, 20%→80V), if ASIM=10%
is set and VM-Vm > 40V, the relay is in
alarm. There is the reset for the value
obtained with 40V reduced by 12%,
that is 35V, thus 35V is the reset value.
There are 2 not-programmable
controls: PHASE SEQUENCE and
PHASE FAILURE (See Tab. A).
PHASE SEQUENCE: if the phases
L1, L2, L3 are present at pins 5-3-1,
the yellow led is ON and the inside
relay is ON. If the phase sequence is
different, the yellow led “flashes” and
the inside relay is OFF.
PHASE FAILURE: if for one of the 3
phases V<0,6VN occurs
(Ex. VN=400V→V<240V), the leds SP
and ASYM flash and the inside relay
goes OFF.
The triggering time of these 2 controls
is < 2 seconds.
The device is self-supplied by the
voltages present at pins 5 and 3, if the
decrease concerns these voltages the
relay can go OFF.
USE
Monitoring of a three-phase mains.