Examine the Online Catalog of Industrial Supplies for Emirel
Great Offers at Unbeatable Prices
Extensive Selection
Quick Shipping
Sale of any product from the catalog Emirel
Brand name
Emirel
tpl10.product.param.model
VD-04
Country
Italy
tpl10.product.param.purpose
Voltage relay
TECHNICAL FEATURES AND
REGULATIONS
SP (SET POINT)
Max set point (or min) divided in 10
parts to be set on the front by
screwdriver.
T
Timer (0,05÷10 seconds standard)
adjustable by means of a small
screwdriver on the front. The set delay
period starts as soon as the current
exceeds the set value; at the end of
this period the relay can go off.
TC
Initial timer (0,05÷10 sec. standard)
adjustable by means of a screwdriver
on the front. It makes the device “blind”
at the voltage starting, in order to
bypass the voltage spike if it occurs.
This timer activates when the voltage
overcomes Im (5% of the max range).
(See Tab. A).
TA (on demand)
self-holding timer 1÷30 sec.
It delays the alarm condition for the set
time, even after the alarm origin has
already gone out.
MODE OF OPERATION
The device can be programmed for
max or min set point.
At the start up of the machine, the
eventual spike of voltage is bypassed
by the timer TC. During normal
operation the set point triggers after
the delay time T.
than 30m.
INPUT
Input resistance: > 8,5 kohm/V.
Permanent overcoming of the value of
RANGE (See Tab. C).
Pin 3-5 (+ on pin 5) (fig. 3).
OUTPUT: 5A 230Vac resistive load
7-6 NC Device not supplied
7-8 NO or in alarm
SUPPLY
2VA - 50-60Hz ±10%
1-11: 115 Vac or 230Vac or 24Vac.
INSULATION
Galvanic separation it is given by the
supply transformer.
SIZE: 48x96x90 mm - undecal male
base. Accessories available on
request: E 171: hooks for flush
mounting; E 172: undecal female base
for DIN; M 13A: plexiglas protection IP
54-tight closure (for flush mounting);
E 346: hold wire protecting from
vibrations.
Template: 45x92 mm
WORKING TEMPERATURE: 0÷70°C
WEIGHT: Kg 0,220 COLOUR: black
FUNCTION
This unit is designed to monitor the
direct voltage of a line or of a logic.
USE
It is used to monitor the DC supply of a
machine or for fixing a set point for a
voltage correspondent to a physical
value. TYPICAL APPLICATION: a set
point for the output of a static
transducer.
- Delivery of spare parts and industrial equipment throughout the USA by Fedex transport company.
- Flexible payment system accepting bank transfers, MasterCard, VISA, PayPall, App Pay, Google Pay.
- Directly from stock and on order.