Examine the Online Catalog of Industrial Supplies for EUROGI
Great Offers at Unbeatable Prices
Extensive Selection
Quick Shipping
Sale of any product from the catalog EUROGI
Brand name
EUROGI
tpl10.product.param.model
EFI.02
Country
Italy
tpl10.product.param.purpose
Indicator
FEATURES | EFI.02 | EFI.05 | EFI.06 | EFI.07 | |
Earth fault trip current (values are customer defined) | Single current value | • | |||
Up to 4 values (jumpers selectable) | • | • | • | ||
Min. Fault Duration (Delay) (values are customer defined) | Single time value | • | |||
Up to 4 values (jumpers selectable) | • | • | • | ||
Visual Fault Signalling (main unit) | Flashing ultra-bright single LED | • | • | • | |
Flashing ultra bright LED LAMP with red dome | • | ||||
Power Supply | Self-powered by internal lithium battery (10 years lifetime) | • | • | • | • |
Remote Fault Signalling (SCADA) | 1NO + 1NC relay momentary contact (500ms) | (o) | • | • | • |
1NO + 1NC relay permanent contact | (o) | (o) | (o) | (o) | |
Automatic RESET after time delay (values are customer defined) | Single time value | • | |||
Up to 4 values (jumpers selectable) | • | • | • | ||
Mains 230Vac RESET | • | • | • | • | |
Pushbutton (manual) RESET | • | • | • | • | |
Remote RESET by NO contact (SCADA) or remote pushbutton | • | • | • | ||
Installation | Wall mount | • | • | • | |
Panel mount DIN 48 x 96 | • | ||||
Load current RESET | (o) | (o) | (o) | ||
Connection for External Indicator | (o) | (o) | (o) | (o) |
EFI02 is the earth fault passage indicator device designed for MV networks, that provides earth fault alarm signalling by a flashing LED when a flow of earth fault current has occurred. The EFI02 device is composed by a IP55 box that contains the electronic module which is connected to an external current transformer placed around the MV cable. It is self-powered by means of the internal battery that ensures 10 year lifetime.
By pressing the pushbutton on the front, it is possible to check the operation of the whole range of cable fault passage indicators.
The earth fault passage indicators are fully tested and calibrated in the factory, without need of any further action. Once installed, the indicators are ready to operate. The earth current is continuously checked by the device, which turns into fault mode - with the LED flashing once per second - when the earth current exceeds the trip level for more than the delay time.
Please see the product manual to get more information about the operating modes and the ways to reset the device.
- Delivery of spare parts and industrial equipment throughout the USA by Fedex transport company.
- Flexible payment system accepting bank transfers, MasterCard, VISA, PayPall, App Pay, Google Pay.
- Directly from stock and on order.