POWER SUPPLY | 5..30 Vdc (loop powered) |
RESPONSE TIME | <220 ms (<;620 ms with rejection 50-60 Hz) |
ACCURACY CLASS | 0,1% |
INPUT CHANNEL | • Pt100 Standard: EN 60751/A2 (ITS-90) Measuring range: -200..+650°C Minimum Span: 20°C 2,3,4-wire connection • Ni100 Measuring range: -60..+650°C Minimum Span: 20°C 2,3,4-wire connection |
OUTPUT CHANNEL | CURRENT (mA) 4..20, 20..4 mA (2-wire) |
THERMAL DRIFT | < 100 ppm (30 ppm tipical) |
PROGRAMMING | EASY SETUP software (programming kit: start / end of scale measurement, connection and RTD type, rejection, measurement filter, cable resistance, fault / over-range output) |
OPERATING TEMPERATURE | -40..+85°C |
CONNECTIONS | Spring clamps |
DIMENSION (ØXH) | Ø 43,7 x 20 mm |
STANDARD | CE |
NORMS | EN 61000-6-4, EN 61000-6-2 |
The T120 is a small, cylindrical device intended for use in industrial or commercial applications. It has a diameter of 43.7mm and a height of 20mm, making it easy to install in a variety of settings. The operating temperature range is -40 to +85°C, allowing it to function in harsh environments.
The T120 is designed to be powered by loop power, with a voltage input range of 5-30VDC. It boasts a thermal drift of less than 100 ppm, with a typical rating of 30 ppm, ensuring accurate readings even in fluctuating temperatures. It can work with different sensing elements and is compatible with a range of control systems.
Overall, the T120 is a reliable and versatile device intended for industrial and commercial use. Its robust design and range of features make it an ideal choice for those needing accurate and reliable measurements in demanding environments.